A-A-51623A
Defects. |
Any component of the bath is missing. |
Any component of the bath is fractured, split, cracked, punctured, cut, dented, sprung, malformed, creased, or otherwise impaired, affecting serviceability. |
Any part is misplaced, loose, or not in proper alignment, affecting serviceability. |
Temperature range of the dial thermometer is not as specified. |
Motor rating is not as specified. |
Turbine ejector lowering and raising device is not free from jams or binds. |
Top edge of tank is not a smooth, beaded rim. |
Bath is not free from cracked, broken, or unsound welds. |
Bath is not free from sharp edges, burrs, or metal slivers. |
Exposed welds are not ground smooth to blend with adjacent surfaces. |
Welds are not continuous, not clean, not free of pitting, splatter, and discoloration. |
Bath finish is not uniform or not free of course grind marks and scratched areas. |
Bath is not clean, not free of dirt, oil and grease. |
Instructions for installation, operation, and maintenance of bath are not furnished. |
Sampling for tests. Sampling for tests, including dimensional test, shall be conducted in accordance with MIL-STD-105, with an AQL of 2.5 (percent defective) and an inspection level of S-3. The unit of product for test purposes shall be one whirlpool bath.